USING TIO2 NANOFLUID FOR ENHANCING PERFORMANCE OF A WATER CHILLER
Abstract
In the present work an experimental study is carried out to enhance performance of water chiller system by using nanofluid (water+TiO2 ) in shell side of chiller with different volume concentration (0.05% , 0.075% and 0.1%) . Experimental work includes two parts; In the first one COP of the system is calculated by using two alternative refrigerants (R-407c and R-134a). In the second part, the optimum COP is fonnd using various concentration of TiO2 nanofluid for system with alternative refrigerant. Experimental results show that the COP of R-134a is better than R407c which will be used in the second part of the present study with nanofluid in shell side of the system. The COP with (0.1%) nanofluid has been found to increase by (8.5%).