TY - JOUR ID - TI - Frequency reduction effect on the performance of thermal power plants انخفاض التردد وتأثيره على أداء محطات القدرة الحرارية AU - Omer K. Ahmad عمر خليل احمد PY - 2015 VL - 10 IS - 4 SP - 330 EP - 349 JO - Kirkuk Journal of Science مجلة كركوك للعلوم SN - 30054788 30054796 AB - This research study the effect of frequency reduction of national electric net on the thermal power plant efficiency. The Baiji thermal station was selected as mathematical model. This steady showed that the frequency reduction due to the increasing of load in the national electric net from 50 Hz to 49 Hz causes that the plant efficiency decrease from (35.9%) to the (33.5%), and the overall efficiency was decreased to 31.3% at 48 Hz because the relationship between this decreasing with the induction working motor in the plant

يهدف البحث الحالي إلى دراسة تأثير انخفاض التردد في الشبكة الوطنية العراقية على أداء محطات القدرة الحرارية العاملة حيث تم اختيار محطة بيجي الحرارية كنموذج رياضي. بينت الدراسة إن انخفاض التردد الناتج من زيادة الحمل المؤثر في الشبكة الوطنية من ( Hz50) إلى ( Hz49) وأحيانا (48 Hz) يؤدي إلى انخفاض في الكفاءة الإجمالية للمحطة من (35.9%) إلى (33.5%) وانخفضت الكفاءة الإجمالية إلى حوالي 31.3% عندما كان تردد الشبكة الوطنية 48 Hz، نتيجة ارتباط هذا الانخفاض بأداء الأجهزة المساعدة في المحطة خصوصا تلك التي تدار بالمحركات الحثية. ER -