TY - JOUR ID - TI - THE EFFECT OF PROXIMITY OF EARTHING CABLE AND POWER CABLES ON THE OPERATION OF EARTH FAULT PROTECTION UNIT AND CATHODIC PROTECTION تأثير تقارب الموصل الارضي وموصلات القدرة على عمل وحدة الحماية ضد الخطأ الارضي والحماية الكاثودية AU - داود مشير جاسم PY - 2010 VL - 3 IS - 3 SP - 297 EP - 310 JO - Al-Qadisiyah Journal for Engineering Sciences مجلة القادسية للعلوم الهندسية SN - 19984456 24117773 AB - This work discusses the effect of proximity between the grounding cable and power cables of high hp 3-ph induction motor, on the operation of the unit of protection against earth fault current and on the system of cathodic protection of the pipes in deep wells, due to high circulating current of grounded cable, induced by the magnetic flux of a 3-ph current of induction motor because of the proximity effect. The work contains practical beneficial experiments, in the work site, for measuring circulating currents, theoretical analysis, useful Conclusions and a very useful recommendation to the engineers deal with this field. It is shown that the reason of circulating current in the earthing cable and the cathodic protection cable is the neighboring of earthing cable to the power cables

ان هذا العمل يتطرق الى تاثير التقارب بين الموصل الارضى وموصلات القدرة في المحركات الحثية الثلاثية الاطوار ذات القدرة الحصانية العالية على عمل منظومة الحماية ضد التوصيل الارضي وعلى عمل منظومة الحماية الكاثودية لانابيب الابار العميقة نتيجة التيار الدوار المتولد فى موصل التأريض بسبب الفيض المغناطيسى المتولد من التيار المار فى موصلات التغذية المسايرة للموصل الارضي. يتضمن البحث تجارب عملية مجدية في حقل العمل لقياس التيارات الدوارة وتحليلات نظرية واستنتاجات وتوصيات مفيدة جدا للمهندسين العاملين في هذا المجال. واثبت بأن سبب التيار الدوار في موصل التأريض وفي موصل الحماية الكاثودية هو مجاورة موصل التأريض الى موصلات القدرة. ER -