TY - JOUR ID - TI - دراسة عملية لبيان تأثير الصمام النبضي على أداء دورة التثليج الانضغاطية AU - محمد رضا جواد PY - 2014 VL - 22 IS - 3 SP - 646 EP - 655 JO - Journal of University of Babylon مجلة جامعة بابل SN - 19920652 23128135 AB - In this research, an experimental study the effects of solenoid valve on the performance of compression refrigeration cycle, when it was placed before the evaporator at the refrigeration cycle. Different air temperatures and velocities entering to the evaporator in. Three speeds of the air entering the evaporator which are (3.5, 11.5, 19.5) m / s and four temperatures of the air entering the evaporator are (18, 22, 26, 30) Co. Experimental works were carried out on the refrigeration system for two cases, with and without the solenoid valve.The experimental results Showed that using the solenoid valve increase the coefficient of performance by (8.125%), the refrigerating effect by (1.22%) the compressor work and mass flow rate reduced by(2.4%) and (6%) respect the air velocity (3.5m / s),and the temperature input to evaporator is (30Co).

تم في هذا البحث إجراء دراسة عملية لبيان تأثير الصمام النبضي على أداء دورة التثليج الانضغاطية. تم وضع الصمام النبضي في وحدة التثليج قبل المبخر ولمدخلات مختلفة لسرعة الهواء ودرجة حرارته الداخلة للمبخر، حيث تم استخدام ثلاث سرع للهواء الداخل للمبخر وهي (3.5, 11.5, 19.5) m/s وأربع درجات حرارة وهي (18, 22, 26, 30) Co. حيث إن الاختبارات العملية على منظومة التثليج تم إجراءها لحالتين،الأولى بعدم وجود الصمام النبضي والثانية بوجود الصمام النبضي.أظهرت النتائج العملية بان إضافة الصمام النبضي لدورة التثليج يولد زيادة (8.125%) في معامل الأداء ، والتأثير ألتثليجي يزداد بمقدار (1.22%) ، وشغل الضاغط ينخفض بمقدار (2.4%) والتدفق الكتلي ينخفض بمقدار (6%) عند سرعة هواء (3.5m/s) ،ودرجة حرارة هواء داخلة للمبخر (30Co). ER -