Experimental Perspective Assessments for a Proper Refrigerant Alternative to R-22 in a Window-Type Air Conditioning Unit
وجهة نظر لتقييم تجريبي لاستخدام مائع تثليج مناسب بديلاً لفريون-22 في وحدة تبريد هواء من النوع الشباكي

Authors: Ameera Yaseen Salim --- Ali Hussain Tarrad
Journal: Journal of Engineering مجلة الهندسة ISSN: 17264073 25203339 Year: 2009 Volume: 15 Issue: 2 Pages: 3756-3775
Publisher: Baghdad University جامعة بغداد

Loading...
Loading...
Abstract

The present research is concerned with the future phase-out of halocarbon types of refrigerants used in the vapor compression refrigeration systems. A window-type air conditioner is selected for the tests to be conducted with two different refrigerants. It is well known that these cooling units are wide spread in their applications and are circulating R-22 as a refrigerant. It is intended to replace this type of refrigerant by another type which is considered to be as environmental friendly refrigerant for smooth operation. The refrigerant selected for this object was R-407C for its favorable thermal properties and acceptable pressure and temperature ranges. The effect of replacing this refrigerant as a substitute on the performance of the cooling unit was studied. The performance characteristics comprise of cooling capacity (Q evap ), power consumed by the compressor (W ̇_cons ) and the coefficient of performance (COP) of the air conditioning unit were obtained. The results showed that the pressure ratio of the R-407C for a proper operation was higher than that of the R-22 by a mean value of (13) %. The power consumed per ton of refrigeration by the unit when circulating R-407C was about (19) % greater than the R-22 values for the whole range of tests. Further, the experimental work has revealed that the actual COP of the unit was reduced by (17) % when circulating the alternative R-407C for the test conditions. The results also showed that this alternative for the present refrigerant with existing cooling unit requires the attention to the mass flow rate of refrigerant circulated and the pressure and temperature ranges throughout the system.

يهتم البحث الحالي بالإيقاف المستقبلي لاستخدام موائع التثليج الهالوكاربونية والتي يدخل في تركيبها الكيميائي الغازات الهالوجينية في منظومات التبريد ألإنضغاطية. لقد تم اختيار مكيف هواء من النوع الشباكي لإجراء التجارب العملية ولمائعي تثليج مختلفين. ومن المعروف إن هذه الوحدات واسعة الانتشار بالاستخدام وتعمل بواسطة تدوير (Freon-22) كوسيط للتبريد. لقد كانت الرغبة باستخدام مائع تثليج قليل التأثير السلبي على البيئة وله القابلية على تشغيل الوحدة بصورة طبيعية. لقد وقع الاختيار على (Freon-407C) كبديل مناسب خلال البحث الحالي نظراً لما يتميز به من مواصفات حرارية مفضلة وله القابلية للعمل بمديات مقبولة من حيث درجة الحرارة والضغط. تم دراسة التأثير الناتج من استخدام هذا المائع على أداء وحدة تكييف الهواء موضوع البحث. إن دراسة الأداء لوحدة التبريد تتضمن حساب كلاً من حمل التبريد (Q evap )’ الطاقة المستهلكة من قبل الضاغط (W ̇_cons ) ومعامل الأداء (COP).لقد بينت النتائج لهذه الدراسة إن نسبة الضغط بين جانب الدفع والسحب للضاغط لمائع التثليج (Freon-407C) ولعمل مستقر ومناسب للوحدة كان أعلى مما عليه في حالة استخدام (Freon-22) كمائع للتثليج وبمعدل ( %13). الطاقة المستهلكة لكل طن تثليج باستخدام (Freon-407C) كانت أعلى بمقدار (19 %) من مثيلتها لحالة (Freon-22) ولكل مدى التجارب الحالية. بالإضافة لذلك فان النتائج العملية قد بينت بان معامل الأداء لوحدة التكييف قل بمقدار (17 %) عند تدوير (Freon-407C) عبر منظومة التبريد. كما وبينت الدراسة الحالية بان البديل المقترح عند استخدامه في منظومات التبريد يتطلب الاهتمام بمعدل التدفق ومديات الضغط التشغيلي ودرجة الحرارة عبر المنظومة.


Article
A QUASI-STEADY STATE OPERATION MODE OF ALTERNATIVE REFRIGERANTS FOR R-22 IN WATER CHILLERS
ألطور التشغيلي الشبه مستقر لبدائل التثليج لفريون R-22 لوحدات إنتاج الماء المثلج

Loading...
Loading...
Abstract

The zeotropic blends comprise of R-407C and R-404A refrigerants and the pure R-134a were selected as a drop-in substitutes for R-22 in a water chiller under a quasi-steady state operation. When comparing the performance of the refrigerants with those of R-22, the results showed that R-407C, R-404A and R-134a reduced the cooling capacity up to (6) %, (6-12) % and (18) % respectively. R-134a and R-407C exhibited higher power consumption per ton of refrigeration than that experienced with the R-22 tests by (8-28) % and (7) % respectively. Whereas, R-404A showed a lower corresponding value than that of the R-22 by (9) %. The R-407C and R-404A showed a significant reduction in the actual (COP) by (19-23) % and (22-55) % respectively. The (COP) of the R-134a showed oscillation when compared with R-22 ranging from (22) % lower at high water inlet temperature to (29) % higher at low water inlet temperature.

تم استخدام موائع التثليج المكونة من خلائط زيوتروبية والمؤلفة من R-407C و R-404A بالإضافة إلى المائع النقي R-134a كبدائل لمائع التثليج R-22 في وحدة تبريد الماء لظروف تشغيلية شبه مستقرة من دون إجراء أي تحوير على منظومة التبريد. عند مقارنة النتائج فقد أبدت جميع البدائل نقصان لسعة التبريد تصل إلى (6) % للمائع R-407C و (6-12)% للمائع R-404A في حين كانت حوالي (18) % لمائع التثليج R-134a. المائعان R-134a و R-407C قد أبديا طاقة مستهلكة لكل طن تبريد بقيمة أعلى عند مقارنتها بتلك المستهلكة


Article
EFFECT OF USING R-22, R404 AND R-407C ON PERFORMANCE OF AN AIR-CONDITIONING SYSTEM
على اداء منظومة التثليجR-22, R404 AND R-407C تاثير استخدام

Author: Abeer Hashim Falih*
Journal: Journal of Engineering and Sustainable Development مجلة الهندسة والتنمية المستدامة ISSN: 25200917 Year: 2018 Volume: 22 Issue: 5 Pages: 200-214
Publisher: Al-Mustansyriah University الجامعة المستنصرية

Loading...
Loading...
Abstract

Due to the environment depletion, replacing chlorofluorocarbons in refrigeration industry was an important problem. In the experimental study a (1.0 TR) vapor compression system were used with original working fluid of R-22 and compared to alternatives refrigerant R-407C and R-22. The effects of the main parameters of performance analysis such as refrigerant type, compressor pressure ratio, outlet air evaporative temperature, coefficient of performance were investigated for various ambient temperatures above 50 ºC. The results showed that the compressor ratio of system using R404 and R-407C is more than the compressor ratio of system using R22 by 2% and 4% respectively. Also, the outlet air evaporative temperature of system using the alternative refrigerant R-22 is more than the outlet air evaporative temperature with system using R-407C and R-404 by 8% and 5% respectively. The coefficient of performance of R-407C was measured with the same reciprocating compressor that was supplied with the R-22 system. It could be concluded that there is a decrease of 8% in system COP as friendly environment R407C compared with system using R-22 and a decrease of 12% in system COP when using R-404. However; the result showed that R407C have thermodynamic performance similar to R-22. Engineering Equation Solver (EES) software is used for draw (p-h) diagram for the cycle